LV OVERHEAD CABLE EARTHING AND SHORT-CIRCUITING DEVICE
Return to listReference : DBTI
Short-circuiting device for twisted LV isolated overhead networks. ICC 4 k A / 1s
The short-circuiting device consists of 11.1 mm diameter (5, 6 or 7 mm diameter depending on the model) bayonet-locking socket junctions, connected by 16 mm² cables from junction blocks.
The distance between each socket is 0.5 m.
Insulated socket junctions affix to the pin of the 6Kv shorting connectors (ref CMCC CT)
One of the connections is left free for possible affixing of the earthing device ref ref. E16L16B or T16L16B
Possibility of providing this device equipped with an NFC TAG:
Radio frequency standard ISO 14443-A (NFC FORUM type 2 – 144 Bytes mini.
The presence of the TAG enables identification and traceability of periodic calibrations
Delivered in plastic box (ref COFFRETP9) 309 x 282 x 100 mm
Complies with standard: IEC 61230. ICC 4 kA/1s.
Models
Ref | Designation | ENEDIS Nomenclature | Weight | |
---|---|---|---|---|
DBTI 5 | 5-socket device | - | 1.25 Kg | |
DBTI 7 T | 7-socket device and NFC tag | 37.15.223 | 1.65 Kg | |
DBTI 6 | 6-socket device | - | 1.45 Kg | |
DBTI 6 T | 6-socket device and NFC tag | 37.15.222 | 1.45 Kg | |
DBTI 7 | 7-socket device | - | 1.65 Kg |